ADEMCO VISTA-120 Guia de Configuração Página 20

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 53
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 19
Vista 120 Training Guide
20
VISTA 120 PROGRAMMING FORM
Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for programming these
fields. Standard default (*97) values are shown in brackets [ ], otherwise default = 0.
*24 IGNORE EXPANSION [0]
ZONE TAMPER 1=Ignore; 0=Enable tamper for RF and RPMs.
*25 BURG.TRIGGER FOR [1]
RESPONSE TYPE 8 1=enable; 0=disable
*26 INTELLIGENT TEST REPORTING [0] 1=yes, (no report sent if any other report was recently sent); 0=no.
*27 TEST REPORT INTERVAL | | [024]
001-999; 000=no report; Enter interval in hours.
*28 POWER UP IN PREVIOUS STATE [1] 1=yes; 0=no
*29 QUICK ARM Partition-Specific
*30 MULTIFREQUENCY OR [0] ( 1 = Recommended )
PULSE DIAL 1=Multifrequency (DTMF); 0=Pulse Dial
*31 PABX ACCESS CODE | | | |
Enter 00-09; B-F (11-15)
*32 PRIMARY SUBS. ACCT # Partit ion-Specific
*33 PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*34 SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*35 DOWNLOAD PHONE No.
Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2 second pause
*36 DOWNLOAD ID No. | | | | | | | |
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
*37 DOWNLOAD COMMAND ENABLES 0 [1]
Dialler System Restrict Remote Remote Remote Upload Download
Shutdwn Shutdwn Access Bypass Disarm Arm Prog Prog
See field 1*53 for Callback disable option; 1=enable; 0=disable
Restrict Download Access When Armed: Can only arm unarmed partitions,
upload the programme/ event log, command relays, and request status
*38 PREVENT ZONE XXX BYPASS Partition-Specific
*39 ENABLE OPEN/CLOSE REPORT Partition-Specific
FOR INSTALLER CODE
*40 OPEN/CLOSE REPORT
[0]
FOR KEYSWITCH 1=enable; 0=disable
*41 NORMALLY CLOSED or EOLR
[1]
(Zones 2-8) 1=N.C. loops; 0=EOLR supervision
*42 SUPPRESS FIRE ALARM RELAY 1= suppress fire alarm relay on 4204/Powerline Carrier Device relays
0= 4204/Powerline Carrier Device fire alarm relay activates on fire alarms
Vista de página 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 52 53

Comentários a estes Manuais

Sem comentários