ADEMCO Vista-128B PLUS Guia de Configuração Página 6

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 72
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 5
– 6 –
*35 DOWNLOAD PHONE NO.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*36 DOWNLOAD ID NO.
|
| | | | | | |
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
*37 DOWNLOAD COMMAND ENABLES
Dlr Shtdwn
Sys Shtdwn
0
Not Used
Rmt Byp
Rmt Disarm
Rmt Arm
Upld Pgm
Dwnld Pgm
See field 1*53 for Callback disable option; [1=enable];
0=disable. For UL installations, all entries must be "0."
*38 PREVENT ZONE XXX BYPASS [000] | |
001-250; 00 if all zones can be bypassed
*39 ENABLE OPEN/CLOSE REPORT FOR [1]
INSTALLER CODE 1=enable; 0=disable
*40 OPEN/CLOSE REPORT FOR KEYSWITCH [0]
1=enable; 0=disable
*41 NORMALLY CLOSED or EOLR (Zones 2-8) [0]
1=N.C.loops; 0=EOLR supervision.
Must be "0" for UL installations.
*42 DIAL TONE PAUSE [0]
0=5 seconds; 1=11 seconds; 2=30 seconds.
Must be "0" UL Installations.
*43 DIAL TONE DETECTION [1]
1=wait for true dial tone; 0=pause, then dial
*44 RING DETECTION COUNT [00] |
01-14; 15=answering machine; 00=no detection.
Must be "00" for UL Burglary.
*45 PRIMARY FORMAT [1]
0=Low Speed; 1=Contact ID; 2=ADEMCO High Speed;
3= ADEMCO Express
*46 LOW SPEED FORMAT (Primary) [0]
0= ADEMCO Low Speed; 1=Sescoa/Radionics
*47 SECONDARY FORMAT [1]
0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed;
3= ADEMCO Express
*48 LOW SPEED FORMAT (Sec.) [0]
0= ADEMCO Low Speed; 1=Sescoa/Radionics
*49 CHECKSUM VERIFICATION [0] [0]
1=yes; 0=no Prim Sec
*50 SESCOA/RADIONICS SELECT [0]
1=Sescoa; 0=Radionics
*51 DUAL REPORTING [0]
1=yes; 0=no If used with Spilt Reporting "1" option (1*34),
alarms and alarm restores go to both primary & secondary
numbers, while all other reports go to secondary only. If used
with Split Reporting "2" option, alarms and alarm restores go to
both, open/close and test messages go to secondary only,
while all other reports go to primary.
*52 STANDARD/EXPANDED REPORT FOR PRIMARY
[0 0 0 0 0 0]
Alarm
Rstr
Byp
Trbl
O/C
LoBat
0=standard; 1=expanded;
Note: Expanded overrides 4+2 format.
*53 STANDARD/EXPANDED REPORT FOR SECONDARY
[0 0 0 0 0 0]
Alarm
Rstr
Byp
Trbl
O/C
LoBat
0=standard; 1=expanded;
Note: Expanded overrides 4+2 format.
*54 UNATTENDED MODE [1]
0=No, 1=Yes, if automatic downloads will be allowed
*56 DYNAMIC SIGNALING DELAY [00] |
Select the delay time (00-15) times 15 seconds before sending
to second destination.
*57 DYNAMIC SIGNALING PRIORITY [0]
0=Primary dialer; 1=LRR, as first reporting destination.
*58 LRR CENTRAL STATION #1 CATEGORY ENABLE
[0 0 0 0 0 0]
Alarm
Trbl
Byp
O/C
Syst
Test
0=disable, 1=enable for reports for primary subs ID of LRR
*59 LRR CENTRAL STATION #2 CATEGORY ENABLE
[0 0 0 0 0 0]
Alarm
Trbl
Byp
O/C
Syst
Test
0=disable, 1=enable for reports for secondary subs ID of LRR
ZONE TYPE RESTORE ENABLES
*79 FOR ZONE TYPES 1-8
1
2
3
4
5
6
7
8
1=enable; [0=disable]
*80 FOR TYPES 9, 10 and 16
9 10 16
1=enable; [0=disable]
*83 FIRST TEST REPORT TIME | | |
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00-
59; 00 in all boxes = instant (Day 01= Monday)
*84 SWINGER SUPPRESSION [01] |
01-15 alarms
Must be "00" (disabled) for UL.
*85 ENABLE DIALER REPORTS FOR PANICS & DURESS
1=enable; [0=disable]
995
996
999
Duress
*87 ENTRY WARNING [1]
1=continuous; 0=3 beeps
*88 BURG. ALARM COMM. DELAY [1]
1=30 seconds; 0=no delay
Must be "0" for UL installations. SIA Guidelines: Must be “1”.
*89 RESTORE REPORT TIMING [0]
0=Instant; 1=After bell timeout if zone is restored; 2=when
system is disarmed. Must be "0" for UL installations.
*90 SEC. SUBS. ACCT # | | | |