VISTA 100 SINGLE PARTITION PROGRAMMING FORM
*00 INSTALLER CODE | | |
Enter 4 digits, 0-9 [5140]
*08 TEMPORAL SIREN PULSE [0]
1 = Yes; 0 = No
*09 ENTRY DELAY #1 [02] |
00-15 times 15 seconds
Maximum "03" for UL Commercial Burglary installations.
*10 EXIT DELAY #1 [03] |
00-15 times 15 seconds
Maximum "04" for UL Listed installations.
*11 ENTRY DELAY #2 [06] |
00-15 times 15 seconds (must be longer than Entry Delay #1)
Maximum "03" for UL Commercial Burglary installations.
*12 EXIT DELAY #2 [08] |
00-15 times 15 seconds (must be longer than Exit Delay #1)
Maximum "04" for UL Commercial Burglary installations.
*13 BELL 1 TIMEOUT [04] |
01-15 times 2 minutes. Minimum 16 min. for UL Commercial
Burglary and 6 min. for Commercial Fire.
*15 KEYSWITCH ASSIGNMENT [0]
Enter partition in which keyswitch used,
1-8; 9=Silences bells if fire alarm
present; 0=disable
*16 BELL 1 CONFIRMATION OF ARMING DING [0]
1=enable; 0=disable. Must be "1" for UL Burglary Installations.
*17 AC LOSS KEYPAD SOUNDING [0]
1=yes; 0=no
*18 BELL 1 AC POWER LOSS ALARM [0]
1=yes; 0=no. Must be "1" for UL Commercial Burglary.
*19 RANDOMIZE AC LOSS REPORT [0]
1=10-40 min; 2=6-12 hrs; 0=normal report (about 2 min.
after AC loss). Must be "2" for Central and Remote
Station Fire alarm systems.
*20 VIP MODULE PHONE CODE | |
Enter 01 - 09 for the first digit; enter [00] , [00]
11 for "
*
" or 12 for "#" for the second digit. This field
Must be set to "0" for Commercial Fire & UL
Commercial Burglary installations.
*22 KEYPAD PANIC ENABLE [001]
1=enable; 0=disable 995 996 999
*23 MULTIPLE ALARMS [1]
1=yes; 0=no
*24 IGNORE EXPANSION ZONE TAMPER [0]
1=Ignore; 0=Enable tamper for RF and RPMs. Must be
"0" for UL installations if using these devices.
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
1=enable; 0=disable
*26 INTELLIGENT TEST REPORTING [0]
1=yes, (no report sent if any other report was recently
sent); 0=no.. Must be 0 for Commercial Fire & UL
Commercial Burglary.
*27 TEST REPORT INTERVAL [024] | |
Enter interval in hours, 001-999; 000=no report ; Max.
024 for Commercial Fire & UL.
*28 POWER UP IN PREVIOUS STATE [1]
1=yes; 0=no; "1" for UL.
*29 QUICK ARM [1]
1=yes; 0=no
*30 MAIN DIALER (TOUCHTONE OR ROTARY) [0]
1=TouchTone; 0=rotary
*31 PABX ACCESS CODE | | | |
00-09; B-F (11-15)
*32 PRIM. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
*33 PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*34 SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*35 DOWNLOAD PHONE No.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause
*36 DOWNLOAD ID No.
|
| | | | | | |
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
*37 DOWNLOAD COMMAND ENABLES
0
Dialer System Not Remote Remote Remote Upload Download
Shutdwn Shutdwn Used Bypass Disarm Arm Program Program
See field 1*53 for Callback disable option; [1=enable];
0=disable; For Commercial Fire & UL installations, all
entries must be "0."
*38 PREVENT ZONE XXX BYPASS [00] | |
001-087; 00 if all zones (except Fire zones) can be bypassed
*39 ENABLE OPEN/CLOSE REPORT FOR [0]
INSTALLER CODE 1=enable; 0=disable
*40 OPEN/CLOSE REPORT FOR KEYSWITCH [0]
1=enable; 0=disable
*
41 NORMALLY CLOSED or EOLR (Zones 3-8) [1]
1=N.C.loops; 0=EOLR supervision; Must be "0" for
Commercial Fire & UL.
*42 DIAL TONE PAUSE [0]
0=5 seconds; 1=11 seconds; 2=30 seconds; Must be
"0" Commercial Fire & UL.
*43 DIAL TONE DETECTION [1]
1=wait for true dial tone; 0=pause, then dial
*44 RING DETECTION COUNT [00]
|
01-14; 15=answering machine; 00=no detection.
Must be "00" for Commercial Fire & UL Burglary.
*45 PRIMARY FORMAT [0]
0=Low Speed; 1=Contact ID; 2=Ademco High Speed;
3=Ademco Express
*46 LOW SPEED FORMAT (Primary) [0]
0=Ademco Low Speed; 1=Sescoa/Radionics