Página 2

2CablingThe panel has high voltage barriers between the a.c. mains supply and the alarmwiring terminals. It is essential that these barriers are maint

Página 3 - Contents

3The control panel enclosure must not be opened before isolating the mains supply.The cover must be securely fitted in normal use.Mains Cable TypeThe

Página 4

4Approval of the Accord xpC is also invalidated if it is used with internal software orsubjected to any hardware modification not authorised by BABT.P

Página 5

5Equipment Electrical RatingThe control equipment is designed to operate on a UK mains supply of 230 Volts a.c.(230 V ±10%) at a frequency of 50 Hz. I

Página 7

7Section 2: Installing the Accord XPCAncillaries PackThe Accord xpC control panel comes with an ancillaries pack. It contains ten zonelinks, a cable c

Página 8

8Removing and Replacing the Accord XPC PCBIf necessary the Accord PCB can be removed from the mountings to aid with enclo-sure mounting and cable wiri

Página 9 - Safety Compliance

9Fitting the Tamper SwitchThe Accord xpC enclosure is supplied without a Tamper Actuator in place. The panelwill not function without a Tamper, it is

Página 10 - Mains Supply Connections

10Connecting Keypads, Sounders and a Speaker to the Accord XPCMounting and Wiring the LED Remote Keypad1. Press down the two base clips recessedon top

Página 11 - Telecoms Approvals

11Connecting the External SoundersConnections for Self Actuating Bells and Bell/Siren combinations should be made asoutlined in table 2.2 and table 2.

Página 13 - Equipment Electrical Rating

12Connecting Power to the SystemMains PowerMains power for the system is 230 V a.c. 50 Hz (a 24-hour unswitched source). Themains cable should be brou

Página 14

13IncomingPSTN LineA BAccord XPC PCBPHONETB52525BT Master socket (NTE5/CTE5).BT Master socket (NTE5/CTE5).Note: Terminals 2 and 5 on the BT Master So

Página 15 - Initial Mounting

14• The SEN of the Accord xpC is 0.3.• Nominal series resistance is 90 milli-ohms.• Nominal insertion loss is 0.1 dB.Note: Difficulties may be experie

Página 16 - To replace the PCB:

15Testing the InstallationPower-up and Initial Test ProcedureWhen the Accord control panel has been installed in accordance with the precedingsafety a

Página 18 - Tip: Use

17Section 3: Programming the Accord XPCImportant: The following programming instructions integrate programming detailsusing both LED and Icon keypads.

Página 19 - ALARM TAMP

18Programming FieldsTo programme a parameter select the programming group. Enter the second digit tochoose the zone number, zone option or system opti

Página 20 - XPC to the PSTN

19Programming Groups 1, 2 and 3 (Zone Programming For Full,Part and Night Set)Programming Groups one to three are used to programme the eight zones fo

Página 21

20Zone Programming — Group 3 Night SetIn programming mode:• The first digit entered is 3 for Night Set.• The second digit is the zone number (1 — 8).

Página 22 - Final Mounting

21SupervisionSelects if the device is to be monitored for presence. This should always be selected as1 (ON) unless the zone is a portable panic button

Página 23 - Testing the Installation

IIIContentsSection 1: Wiring Regulations and Safety Compliance...1General Information ...

Página 24

22SNOITPOMETSYSPUORGNOITPOTLUAFED4emiTtixE=9–1,tcatnoClaniF=0(emiTtixE=1 × .)s01)3(4.)s01×emiTyrtnE=9–1(emiTyrtnE=2)3(4eeS—emiTffo-tuClleB=3 6.3elbaT

Página 25

23Group 4 — Option 1 Exit TimeThis is the amount of time that the user has to exit the premises after initiating a FullSet procedure. Entering 411 wil

Página 26 - Table 3.1 Programming Groups

24—GNINRAWTIXETESTRAP YLNOREZZUBDAPYEK144ENOTTIXETLUAFENOTTLUAFTAENOTFODNEEMITTIXETROFMOCENOTteStraPylnodapyeKylnodapyeKylnodapyeKylnodapyeKteSthgiNen

Página 27 - Part and Night Set)

25• Alarm Condition.• Panic Alarm.• Fire Alarm.This output may be used to trip a transistorized relay for control of auxiliary equip-ment. The alarm t

Página 28 - Table 3.4 Night Set Zones

26Group 5 — Option 1 Audible Warning of AC LossWhen enabled (1) an audible indication is given from the keypad piezo that an a.c.mains failure has occ

Página 29

27Assistance: Press 4+6 together. Keypad displays scrolling LEDs ( ) with fast pulsetone.Fire: Press 7+9 together. Keypad displays scrolling LEDs (

Página 30 - Programming System Options

28Set to 2 (Technistore): User code can cancel a day tamper activation but a Technistorereset number must be entered to reset the system.Set to 3 (Eng

Página 31 - Table 3.7 Bell Cut-off Times

29System Programming - Group 6 Comms Options1Group six programming is as follows:1. The first digit entered is 6 for System Options.2. The second digi

Página 32 - 0. Set (on in any set state)

30Group 6 — Option 5 Downloader Telephone Number.A Downloader Telephone Number of up to 20 digits may be entered. If less than 20digits are used, end

Página 33

31Group 6 — Option 8 Communicator FormatThe Accord xpC panel has three communicator format options:0. Comms disabled.1. High Speed.2. Contact I.D.This

Página 34

IVSection 3: Programming the Accord xpC ...17An Introduction to Programming the Accord xpC...

Página 35

32System Programming - Group #6 Confirm Options (DD243)These options allow the confirmed alarm reporting operation to be modified to taylorthe system

Página 36

33Group #6 - Option 3 Walk Through Affects ConfirmThis selects if a walk through type zones will contribute to confirmed alarms. Thisoption has two se

Página 37

34Group #6 - Option 7 Restart Confirm Time on Repeated Single ZoneWhen this option is enabled (1), the confirm timer will be restarted whenever the fi

Página 38 - Table 3.12 No of Rings

35System Programming — Group 7 Comms Options 2Group 7 — Option 1 Dual ReportingThis option can be programmed in one of two modes:0. Single Report1. Du

Página 39 - 2 = Contact I.D

36Group 7 — Option 2 Dial TypeIf this option is set to 0 the panel dials using Pulse dialling, also known as Rotary orLoop DisconnectIf this option is

Página 40 - 3 Always

372. Push-to-Set on Full Set and Part Set.3. Push-to-Set on Full Set and Night Set.4. Push-to-Set on all set modes.This option defaults to disabled 0

Página 41

38Group 7 — Option 8 Downloader OptionsThis option determines under what set conditions the Ademco Microtech Downloadersoftware may access the Accord

Página 42 - 3 During Entry

39System Programming – Group 8 CommunicationEnable / DisableThis option is used to assign functions tothe communications triggers. The func-tions are

Página 43 - 1 Dual Report

40SNOITPOSMMOC8puorGnoitpOtluafeD1reggirT1lennahC102reggirT2lennahC203reggirT3lennahC304reggirT4lennahC005reggirT5lennahC006reggirT6lennahC007reggirT7

Página 44

41System Programming — Group 9 ParametersSNOITPOMETSYSPUORGNOITPOTLUAFED9.)seY=1,oN=0(senoZdettimOetacinummoC=1)0(9.)seY=1,oN=0(langisteS/tesnUtrevnI=

Página 45

VGroup 6 — Option 9 Central Station (ARC) Receiver Handshake... 31System Programming - Group #6 Confirm Options

Página 46

420. No Zone.1-8. Number of zone for double knock.This option defaults to 0 (No Zone).Group 9 — Option 4 User Omit ZoneThis option has two settings:0.

Página 47 - Table 3.14 Group 8—Triggers

43Group 9 — Option 7 Print Event LogThis option allows the system event log to be printed by a serial printer.0. No Event Log Print1. Print Event LogT

Página 48

44Group 0 Communications & RFGroup 0 — Option 1 Technistore VersionThis option is for use with Technistore reset. The engineer can programme theTe

Página 49 - Table 3.16 System Parameters

45Group 0 — Option 5 Transmitter Supervision Time WindowThis option assigns the supervision time window (0-2.5 hours for class 6).0. 2.5 Hours1. 3.6

Página 50

46Zone Type DefinitionsGeneral InformationThe Accord xpC has ten zone types, these are:0 — Not UsedZones which are unused should be programmed as 0 N

Página 51

47 5 — 24 Hour TamperA 24 Hour Tamper zone is used for system tampers and for zones covering sensitiveareas such as stock rooms, fire doors, external

Página 52

488 — Push-to-SetA Push-to-Set zone becomes active when the setting procedure is initiated. Setting willterminate if the Accord xpC detects a change i

Página 53

49Section 4: Wire Free InstallationInstructions6128RFH Keypad and 5882H Receiver InstallationReceiver TypesThe following notes cover the installation

Página 54 - Zone Type Definitions

50Set-upBoth the 6128RFH and 5882H need to have the addresses set before use with theAccord panel. The receiver must always be set to address 0.6128RF

Página 55

514. Exit programming mode and walk test the detectors to determine the bestlocation for each, and for the receiver/keypad.* Note: Most detectors shou

Página 56

VI1 — Final Exit... 462 — Keyswit

Página 57 - Instructions

52High Security Mode (6128RFH only)For programming secure fobs onto the Accord xpC: (required for DD243)1. Learn the fob onto the 6128RFH keypad first

Página 58 - Wire Free Programming

53Wire Free Installation Hints and TipsNotes on Wire Free detector location:The Ademco Microtech 5800 range of wire free detectors can run at indoor r

Página 60

55Section 5: Operating The AccordSetting and Unsetting the SystemBefore setting the system:• Ensure all doors and windows are secure.• Ensure movement

Página 61 - Walk Test

56Night Set 3 ( )To Night Set the system:• Enter your User Code then press the 3 (Night Set) key.• This starts the setting of the system using the

Página 62

57The Bell output and zone LEDs (No.s), activate for five seconds. The Strobe outputflashes until the test is finished.When the keypad LEDs (No.s) hav

Página 63

58Note: The master user code defaults to 1234, the Engineer Code defaults to 9090.The master user code can reprogramme the other seven user codes. Onl

Página 64

59Example: To enable the Chime function on zones three and five:• Enter your User Code.• Press: 9 3 5.• Two beeps confirm that the Chime function ha

Página 65 - Reprogramming Your Code

60Programming the Time and DateThe time and date may be set through the keypad by entering any valid code andpressing # 0 (Log) then DDMMYYHHMM wher

Página 66 - Programming New User Codes

61Section 6: Systems Indications andWhat they MeanSNOITCNUFDAPYEKDCLDAPYEKDELdapyeKHFR8216EDOMYAD)dilos()dilos(DELYADYDAERdnaCATESLLUF)gnihsalf()gnihs

Página 67 - Printing the Event Log

VIISection 6: Systems Indications and What they Mean...61Section 7: Handing the System Over to the User...

Página 69 - What they Mean

63Section 7: Handing the System Over tothe UserFill In the User Instructions!User Instructions come with every Accord xpC panel. It explains end-user

Página 70

64Remote Keypad SpecificationConnected via a three wire terminal block on the back of the keypad.Built in piezo warning sounderPhysical Width: 120 mmH

Página 71 - Appendix A: Specifications

65Appendix C : Bell-Box ConnectionsThe terminal connections for various bell-box models are shown below..noxeL021/DEL021-.dtLkcetnyLslanimreTdroccA+LL

Página 72 - Depth: 25 mm

66Appendix D: Programming SummaryPROGRAMMING FORMV1.46 PANELSTHE DEFAULT VALUES FOR EACH OPTION ARE SHOWN IN BRACKETSDEFAULT MASTER CODE 1234 (User 1)

Página 73

67Appendix D...contd.SYSTEM OPTIONSGROUP OPTION SELECTION7 1=DUAL REPORTING (0=NO, 1=YES) (0)7 2=DTMF OR PULSE DIALLING (0=PULSE, 1=DTMF) (1)7 3=PRE

Página 74 - PROGRAMMING FORM

68ADEMCO MICROTECH LIMITED WARRANTYAlarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions,subsidiaries and affili

Página 76 - Redditch, B98 9HE

70Ademco Microtech Ltd.3 Wellington CrescentFradley ParkLichfieldStaffsWS13 8RZAdivision of the Pittway CorporationIE1-1232 Issue 3© Copyright Pittway

Página 78 - IE1-1232 Issue 3

1Section 1: Wiring Regulations andSafety ComplianceGeneral InformationIt is essential that this product is installed correctly, in particular with res