Remote Consoles
Console Is Inoperable;
Erratic Display
Power down completely (AC + battety), disconnect the battery, and power up
again (AC only).
Check that auxiliary voltage is between 12.5VDC-14.0VDC. If not, disconnect all
auxiliary
devices, and take another reading. If now within the above range, there
was too much current being drawn by the auxiliary devices. (see the Auxiliary
Device Worksheet for the current draw of each device). If still not within the
above range, check incoming power from the No. 1361 transformer. Voltage
should be 16.5VAC. If below 15VAC, carefully check the AC supply for a
minimum of 110 VAC.
With all auxiliary devices and batterv still disconnected, check the voltaae on the
red & black
bafiery leads. It should be 13.65VDC (approx.). If not, re~lace the
Control. If it is @ 13.65VDC, the battery may not be at full charge (allow the
battery to charge 12-24 hours before reconnecting the auxiliary devices) or the
battery may be bad, and not able to hold a charge.
Hard-Wired Zones, 1-8
Zone 1 in trouble
If zone 1 is programmed for fire (response type 9), make sure that field 146 is
(“CHECK” or “FAULT”)
set to “3” (zone 1 EOLR). Also,make
sure that the RED jumper is intact and that
there is a 2,000 ohm EOLR across the last device, as described in the SYSTEM
CONFIGURATION: ZONES section. All devices must be normally open and
connected in parallel across terminals 9 and 10.
If zone 1 is programmed as a non-fire response type and field 41 is
programmed as a “O”(EOLR required), make sure that the RED jumper is intact
and that there is a 2000 ohm EOLR connected across the last device, as
described in the SYSTEM CONFIGURATION: ZONES section.All devices must
be normally open and connected in parallel across terminals 9 and 10. Check
that field 1
46 is set to “3” (zone 1 EOLR).
c If zone 1 is programmed as a non-fire response type and field *41 is
programmed as a”1” (normall closed loops), make sure that the
RED jumper is
cut, and that normally closed devices are connected
in series between terminals
10 and 12 as described n the SYSTEM CONFIGURATION: ZONES section.
Zones 2-8 not detecting If using EOLRS,check that program field *41=0; if not using EOLRS, 41=1.
faults when their EOLRS
are shorted (READY
display stays on)
Zones 1-8 is not detecting
Check program fields 1•18 and 1•19 to make sure the wired zone(s) in question
faults (READY light stays
have
not been enabled as RF zones.
on)
Hard-Wired Zones On 4219 Wired Zone Expander
Zones on 4219 not
detecting faults
“81” appears in the
console dispiay and rapid .
beeping occurs.
Make sure that RF zones do not overlap any of the 4219 zones.
Make sure that Address 1*58 is programmed correctly and that the correct
response types have been entered for the corresponding zones.
Make sure that the dipswitches on the 4219 are set in accordance with Figure 1
in the section titled WIRED ZONE EXPANSION.
The 4219 wired zone expander is not responding to the control panel.
Check that the control is wired properly to the 4219.
Check that the wire run length is in agreement with the recommended wire
gauge.
Make sure that the dipswitches on the 4219 are set in accordance with Figure 1
in the section titled WIRED ZONE EXPANSION.