VI.
SYSTEM CNCKOUT
Perform these tests after the wiring and option selections desired in
the
1.
2.
3.
4.
5.
6.
previous sections have been canpleted.
Install both the control and the communicator PR@k (No. 691),-into
their respective sockets (see Diagram 4) after making certain that
there is no power going to the system. Take care td align the PfWM
orientation marks.
Install
the PROMS using the No. 692 Insertion'
Tool.
Connect the telephone 1 ine and handsets via a h. 620 Direct Connect
Cord (See Diagram 4).
Connect the battery
by connecting the plug at the end of the black
and
red wires coming from the battery to the socket connector at
the end of black and red wires coming from the circuit board. Rapid
beeping will occur,
0 will briefly appear on the console display
at the upper right, and the READY light will go on.
Enter the security
code and OFF to stop the beeping.
Plug the transformer into a
llOV.AC
‘outlet that is ON 24 hours a
hY*
The POWER LED will light on the Security Console and on the
c-ml.
Observe the Digital Display on the Security Console after depressing
tk READY l&y. lWhing will appear if the protective loops are properly
wired and all contacts are properly set.
Similarly, none of the
.zone status LEDs on the C-COM will be lit.
With 110 alarm or trouble being indicated,
do the following and observe
the response:
a.
Open each of the burglary zones momentarily,
one at a time.
The appropriate zone n.unber should appear on the Security Console
Zone I.D. Display and the appropriate zone LED should light
on the C-COP while the zone is open.
b.
Short each of the burglary zones momentarily.
one at a time.
The appropriate zone number should appear on the Security Console
Zone I.D. Display and the appropriate zone LED should light
on the C-COM while
the
zone
is
shorted.
NOTE: If
Zone
4
has been set up
as a D&Night Zone (trouble by day,
alarm by night), the above actions will also cause the
CHECK
display to light on the Security Console, the CHK.BYP LED on
any Remote Keypad (if used) to light, and the Zone 4 TRBL LED
on the C-COM to lfght.
In
addition, the Security Console and
the Remote Keypad will produce a rapidly pulsing sound.
7.
If
zone 4 has been set up
as a fire
zone, do the following:
a.
Observe the C)(ECK display on the Security Console or the CRK.BYP
LED on any Remte Keypad or the Zone 4 TRBL LED on the C-COW.
They should be off if the protective loop and detector power
circuits are properly wired.