54–
02 Start: Part
Any Partition A
Enter (if applicable) the partition number 1 or 2 (or 0 for any).
Press the [
*
] key to continue.
02 Stop: Zn List
No List 0
If a zone list will be used to STOP, or restore, the device action, enter the zone
list number 1, 2, or 3 (to be programmed in
*
81 mode). If not used, enter 0.
Press the [
*
] key to continue.
02 Stop: Zn Typ
Not Used 00
If a zone type or system operation will be used to STOP the device action, enter
the appropriate two digit code (see the "ZT" choices listed above). If not, enter 00.
Press the [
*
] key to continue.
02 Stop: Part
Any Partition A
Enter (if applicable) the partition number 1 or 2 (or 0 for any). Press the [
*
] key to
continue.
02 A EV ZL ZT P
STT 0 0 0 00 1
This screen again displays a summary of the current device START programming
. Press the [
*
] key to continue.
02 A EV ZL ZT P
STP – – 0 00 A
This screen again displays a summary of the current device STOP programming.
Press the [
*
] key to continue.
02 X10 Device ?
0 = No, 1 = Yes 00
Enter 1 if using a Powerline Carrier Device (X-10); if not, enter 0.
The display then returns again to the first screen so that the next device number
to be programmed can be entered, or enter [0][0] to end device programming.
Example of
Output Device
Programming
A lamp is to be turned on via a Powerline Carrier device (X-10) when any one of 3
specific zones are faulted, or when any 24-hour auxiliary zone is faulted. We want
to be able to turn off the lamp manually without affecting the arming status of the
system.
To program this, we would do the following:
In
*
80 interactive mode we choose Output Device 01 and program the Action
(A) to be "2" (Close and stay closed). The Event we are looking for to
start
the
Device action is a fault, so we will program "2" in (EV). We will use Zone List 1
for the 3 specific zones, so we will program "1" in (ZL), (and we will program
these 3 zones in
*
81's Zone List 1).
The second condition for turning on the indicator is triggering a 24-hour aux.
zone (Zone Type 08), so we will program (ZT) as "08".
Next, enter the Partition number (P) in which you want the triggering of a 24-
hour zone to occur; enter 1 or 2, or enter 0 for
any
partition.
To stop the Device action and turn off the lamp, we do not want to use a restore
of any zone, so a "0" will be programmed for the Restore of Zone List (ZL). We
will use a manual entry of User Code + [#] + [8] + Device # to turn off.
Therefore, we do not need to program a STOP event.
Press [
*]
to continue.
The system will display a summary screen for the START programming for
device 01. Press [
*]
to continue.
The system will display a summary screen for the STOP programming for device
01. Press [
*]
to continue.
The system will display the "X10?" prompt. Enter 1 for yes.
The Enter Device No. prompt for the next zone will be displayed.
Press 00 and then [
*
] to exit the
*
80 mode.
Now use
*
81 Zone List mode to program the 3 specific zones in Zone List 1.