Wireless Options
1*28 RF TX Low Battery Annun.
Enter 0 if audible beep and display annunciation upon RF transmitter low
battery condition is desired only in disarmed state. Enter 1 if audible beep
and display is desired in both armed and disarmed states. Must be 1 for UL.
1*29 RF TX Low Battery Report Enable
Enter 1 if a trouble message for RF transmitter low battery conditions is to
be sent to the central station. Enter 0 if no report for transmitter low battery
is desired. Note that a trouble message will be sent for a transmitter
supervision failure independent of this selection. Must be 1 for UL.
1*30 RF Rcvr Supervision Check-In Interval
Enter the check-in monitoring interval in 2-hour increments. Enter 02-15
times 2 hours (4-30 hours). Failure of a receiver to receive any RF signal
within the time entered will result in activation of the response type
programmed for zone 90 for the first receiver and zone 88 for the second
receiver and their related communication reports. Enter 00 to disable
receiver supervision. Max. "6" (12 hr) for UL.
1*31 RF Transmitter Check-In Interval
Enter the check-in monitoring interval in 2-hour increments; enter 02-15
times 2 hours (4-30 hours). Failure of an individual transmitter to send a
supervision signal within the time entered will result in a trouble response
and related communication report. Entry 00 disables transmitter
supervision. Max. "6" (12 hr) for UL.
1*32 Receiver Type
Enter 0 if using 4280 series Receivers. Enter 1 if using 4281 series
receivers. enter 2 if using 5881 series receivers. Important: the 4281
microprocessor must have part number N5334Vx, where x is any number.
1*44 Wireless Keypad Tamper Detect
Enter 1 to enable tamper detection on wireless keypad. Enter 0 if tamper
detection is not desired. If this feature is enabled, any attempt to tamper by
means of many trial entries at a wireless keypad will be blocked by the
control panel. If more than 40 key depressions are received without a valid
sequence (arm, disarm, etc.), the Control panel will disable the wireless
keypad. The inhibit is removed once a valid key sequence is received from
a wired keypad.
1*48 Wireless Keypad Assignment
Enter the partition in which the RF keypad is used, 1-8. Enter 0 if no RF
keypad is used.
1*49 Disable Trouble Sounder For RF Supervision
Enter 1 to disable trouble sounding for transmitter check-in failure. Enter 0
if audible trouble sounding is desired. Must be "0" for UL.
1*57 Enable 5800 RF Button Global Arm
Enter 1 to have the system arm/disarm in accordance with the button's
user's global arming settings. Enter 0 if the button is not to be used to
global arm the system (however, home partition arming will still occur).
1*58 Enable 5800 RF Button Force Bypass
Enter 1 to allow the RF Button user to force bypass all faulted zones.
When attempting to arm the system, the console will beep once after
pressing the button, if any faulted zones are present. If this feature is
enabled, the user should then press the button again within 4 seconds to
force bypass those zones and arm the system.
Partitioning Options 2*17 Number Of User Codes Per Partition
Enter 01-99 for each partition used in the system. Enter 01 for unused
partitions. Total number of user codes in the system must be less than or
equal to 128. Note that one user number is automatically assigned to each
partition, regardless of whether that partition has been enabled.