Limitation of Access by Time
Worksheet
Limitation of access determines the times a particular user code is active in the
system. The system provides 8 Access Schedules, each of which consists of two
time windows for each day of the week and two time windows for holidays. If
access schedules have been assigned, when a user is assigned, that user's
access to the system can be limited by specifying an Access Schedule number in
the range of 1-8. If no limitations apply, enter 0.
Enter the appropriate time window numbers for each partition.
Acc Monday Tuesday Wed. Thursday Friday Saturday Sunday Holiday
Sch W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2 W1 W2
1
2
3
4
5
6
7
8
Time-Driven Event
Worksheet
These are the schedules used to activate outputs, bypass zones, etc. based on a
time schedule. There are 20 of these events that may be programmed for the
system, with each event governed by the previously defined time windows.
The actions that can be programmed to automatically activate at set times are relay
commands, arm/disarm and zone bypassing commands, and open/close access
conditions.
To fill out the worksheet:
1 ) First enter the schedule number (1-20) and time window
number (1-20), and note the day of the week the action is desired.
2 ) Enter the code for the desired action and action specifier. The
action codes are the events that are to take place when the scheduled time is
reached. Each action also requires an action specifier, which defines the action
code. The action specifier varies, depending on the type of action selected.
The following is a list of the "Action" codes (i.e. desired action) used when
programming time driven events. Note that these codes are independent of
the "relay codes" programmed during the #93 Menu ModeRelay
Programming mode.
Relay commands
Action Code Action Specifier
01 Relay On Relay #
02 Relay Off Relay #
03 Relay Pulse Relay #
04 Relay Pulse XX minutes (set in field 1*74) Relay #
05 Relay Pulse YY seconds (set in field 1*75) Relay #
06 Relay Group On Relay Group #
07 Relay Group Off Relay Group #
08 Relay Group Pulse Relay Group #
09 Relay Group Pulse XX minutes (set in field 1*74) Relay Group #
10 Relay Group Pulse YY seconds (set in field 1*75) Relay Group #
Arm/Disarm commands
NOTE: Activation times 1 (Begin), 2 (End), 3 (During) are the only valid
choices for these commands.
"During" can be used to arm or disarm the control for specific time only. For
example, if "during" is selected with arm-stay, the system will arm-stay at the
beginning of the window and disarm at the end of the window.
Action Code Action Specifier
20 Arm-Stay Partition(s)
21 Arm Away Partition(s)
22 Disarm Partition(s)
23 Force Arm Stay (Auto-bypass faulted zns) Partition(s)
24 Force Arm Away (Auto-bypass faulted zns) Partition(s)