Section 19 - The Mechanics of Programming
19-3
SUMMARY OF DATA FIELD PROGRAMMING COMMANDS
*91
Select partition for programming partition-specific fields
*92
Will display the software revision level of the control panel
*93
Enters Menu Mode programming
*94
Go to next page of fields
*99
Go back to previous page of fields or exit Programming Mode with
no installer code lockout
*98
Exit Programming Mode with Installer Code lockout
Programming System-Wide Data Fields
Values for some programming fields are system-wide (global), and some can be different for
each partition (partition-specific). Note that the partition-specific programming fields are
automatically skipped when programming the global fields. If the system has only 1
partition, the partition-specific fields
will not
be automatically skipped. To program system-
wide data fields, do the following:
1.
Enter Program Mode:
[Installer Code] + 8 0 0 0.
2.
After entry into the Program Mode, the following will be displayed:
Program Mode
*Fill # View -00
3.
If the control has not been programmed before,
enter *97 to load factory defaults.
4.
Press [
✴]
and
enter
the first field number to be programmed
(for example,
∗
00,
Installer's Code). Make the desired entry. When the field is complete, the keypad will
beep three times and will advance to the next field. If you do not desire to change the
next field, press [
✴
]
and enter the next field number to be programmed.
First Page of fields
(*00-*90)
press *99 or *98 to exit Program Mode
5.
If the number of digits that you enter in a data field is fewer than the maximum
permitted (for example, a phone number), the keypad displays the last entry and waits.
To proceed, enter [
✴
]
+ the next data field you wish to program (e.g., press
∗
08).
Partition-Specific Programming Fields are skipped unless entered specifically.
6.
To change to the next page of fields, press
*94
. To return to the previous page of fields,
press
*99
.
Programming Partition-Specific Data Fields
To program partition-specific data fields once in Program Mode, do the following:
1.
Press
*91
, which will prompt you for the partition number desired.
2.
Enter a partition-specific field number (e.g.,
∗
09) to begin programming.
When the first
field’s entry is completed, the next partition-specific field will automatically be displayed.
When all partition-specific fields are programmed, the system returns to the global
programming fields (page 1 fields). To return to the global program fields before
finishing all fields, enter any global field number.
3.
Repeat this procedure for each partition in the installation.
Comentários a estes Manuais