VISTA-128B Installation Instructions
22-10
*87 ENTRY WARNING (partition-specific)
[1]
Enter 0 for 3 short beeps, or 1 for slow beeps that continue for the entire entry delay
period.
*88 BURG. ALARM COMM. DELAY (partition-specific)
[0]
Enter 0 for no delay on burglary alarm communication. Enter
1
for 16-second delay (no
delay on 24-hour reports). Must be 0 for UL installations.
*89 RESTORE REPORT TIMING
[0]
Enter 0 for instant Restore report as zone restores.
Enter 1 for reporting after bell timeout if zone restored. Enter 2 for Restore report
when system is subsequently disarmed. Must be
2
for UL commercial burglary
installation.
*90 SECONDARY SUBSCRIBER ACCT #
|
|||
(partition-specific)
Enter 00-09; B-F (11-15)
[15 15 15 15]
Enter the 3-or 4-digit number (depending on report format) for the secondary subscriber
account: 00-09; B-F (11-15). Each number requires a 2-digit entry to allow entry of
hexadecimal digits (B-F). If a 3-digit number is to be used, enter data only in the first 6
locations, leaving the last two unfilled. Default=15 15 15 15. Erase the field by entering
*90*. NOTE: This field must be programmed if a secondary phone number is used (field
*34). This account number can be the same as the primary account number.
1*07 CHECK OR TRBL DISPLAY
[0]
Enter 1 to display the letters TRBL instead of CHECK when a zone or system trouble
occurs.
Enter
0
to display CHECK.
1*10 FIRE DISPLAY LOCK
[0]
0 = scroll all alarms
1 = lock display of first fire alarm (press * to display other alarms)
1*17 LOBBY PARTITION
[0]
Enter the Common Lobby Partition (1-8).
Enter 0 if none.
1*18 AFFECTS LOBBY (partition-specific)
[0]
Enter 1 if this partition affects the common lobby. Will cause lobby to disarm when this
partition disarms.
Enter 0 if it does not.
1*19 ARMS LOBBY (partition-specific)
[0]
Enter 1 if arming this partition causes the system to attempt to arm the common lobby
partition automatically. Can only arm lobby if all other affecting partitions are armed.
To enable this field, field 1*18 must also be enabled (partition-specific).
Enter 0 if arming this partition will not attempt to arm the common lobby partition.