21-1
SECTION 21
Zone Index/Zone Type Defaults
•••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
♦
Zone Index
♦
Zone Type Defaults
•••••••••••••••••••••••••••••••••••••••••••••••••
Zone Index
The VISTA-128B has 128 protection zones, as well as supervisory zones for relays, ECP
devices (devices which communicate through the keypad terminals), and system troubles.
These zones are designated as follows:
ZONE # RANGE ZONE FUNCTION ACTUAL ZONE
001 - 128 Protection zones As indicated
601 - 632 Relay Supervisory Zones 6 + 2-digit Relay Number; e.g.,
Relay Number 03, if supervised, is
zone 603.
800 - 831 ECP Device Supervisory Zones
(includes keypads, wireless
receivers, VIP Module, relay
modules, etc.)
8 + 2-digit Device Address; e.g.,
Device Address 01, if supervised, is
zone 801. The 4285/4286 VIP
Module is zone 804 (since its
Device Address must be set to 4).
970, 988,-990, & 997 System Supervisory Zones
970: Bell Supervision
988: 2nd Wireless Receiver - not
receiving signals
990: 1st Wireless Receiver - not
receiving signals
997: Polling Loop (short circuit)
995 - 999 Keypad Panics
995: 1 +
∗
panic (A key)
996: 3 + # panic (C key)
999:
∗
+ # panic (B key)
Response types for zones are enabled in
Zone Programming
in the
#93 Menu Mode.
Supervisory zones should be given a response type of 05 (Trouble by Day, Alarm by Night).