VISTA-128B Installation Instructions
6-2
++
-
N.C.
N.C.
N.O.
2k EOLR 2k EOLR
+-
++
-
N.C.
N.C.
2k EOLR 2k EOLR
++
-
N.C.
+
+
-
N.C.
N.C.
2k EOLR
SMOKE
Zone resistance (Excluding EOLR):
ZONE 1,8: 100 OHMS MAXIMUM
ALL OTHER ZONES: 300 OHMS MAXIMUM
ZONE 1
ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9
2-WIRE SMOKE
DETECTOR LOOP
(Also supports NO/NC Burg contacts)
Programmable Response
(Fast/Normal) Loop
LATCHING TYPE GLASS
BREAK DETECTORS
10 11 12 13 14 15 16 17 18 19 20 21 22 23
N.C.
N.O.
N.O. N.O.
2k EOLR
N.O. N.O.
N.O.
N.C.
N.O.
2k EOLR 2k EOLR
N.C.
GLASS
BREAK
Fire
Usage
Burg.
Usage
Red Jumper
Zone response time:
ZONES 1-8: 350mSec-500mSec
ZONE 9: Programmable for
Fast: 10mSec-15mSec
Normal: 350mSec-500mSec
(default response)
Figure 6-1: Wiring Connections for Zones 1-9
Wiring 2-Wire Smoke Detectors to Zone 1
Zone 1 has the added capability of supporting 2-wire smoke detectors. The zone provides
enough standby current (2mA) to power up to 16 of the smoke detectors listed below. The
zone provides only enough alarm current (20mA) to power one smoke detector in
the alarmed state. When assigned zone type 9, the second entry of a User Code + OFF
sequence at a keypad will interrupt power to these zones to allow detectors to be reset
following an alarm.
1. Connect 2-wire smoke detectors across zone 1 terminals (10 through 11) as shown in
Figure 6-1. Observe proper polarity when connecting the detectors.
2. If EOL resistors are presently connected across zone 1 terminals, remove them. The
EOL resistor must be connected across the loop wires at the last detector.
2K EOL resistors must be used on fire zones (standard, discrete 2K EOL resistors may be used on
burglary and panic zones) and must be connected across the loop wires of each zone at the last
detector.
The alarm current provided by zone 1 will support only one smoke detector in the alarmed state
.