
VISTA-15/VISTA-15CN Installation and Setup Guide
23–2
Press [Installer code] + [#] + [3] on the keypad. This initiates a procedure to verify
that all transmitters have been properly programmed.
NOTE:If the communicator is in the process of sending a report to the Central Station,
the system will not go into the Sniffer mode. If so, wait a few minutes, and try again.
The keypads display all zone numbers of wireless units programmed into the system.
As the system receives a signal from each of the transmitters, the zone number of that
transmitter disappears from the display. The transmitter codes may be checked upon
installation, or in an installed system.
All the wireless zone numbers should disappear after about 90 minutes.
NOTES:
• All BR-type units must be physically activated to clear the display.
• When one button of a transmitter (RF, UR, or BR) is activated, all zones assigned to
other buttons on that transmitter are cleared. This also applies to 5816 and 5817
transmitters that have multiple loops (zones).
• Any transmitter that is not “enrolled” will not turn off its zone number.
Exit this mode by keying [Installer code] +
[1]
OFF.
b.
GO/NO GO TEST MODE:
By pressing [Installer code] + [#] + [4] on the keypad, a
mode similar to the user Test mode (code + TEST) is entered, but the wireless receiver
gain is reduced. Checking in this mode assists in determining good mounting locations
for the transmitters when the system is being installed, and verifies that the RF
transmission has sufficient signal amplitude margin for the installed system.
Exit this mode by entering [Installer code] +
[1]
OFF.
NOTE: System Test mode
([Installer code] + [5] TEST) is
automatically terminated
after 4 hours if the installer or user does not manually terminate it. This ensures that fire
and panic zones will not remain disabled. However,
Sniffer mode
([Installer code] + [#] +
[3])
does not automatically expire.
You must manually exit ([Installer code] + [1] OFF)
Sniffer mode to return to normal operation. Sniffer mode also terminates if a user arms the
system.
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent
testing by the user are vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular
maintenance program to the user, as well as acquainting the user with the proper operation
and limitations of the alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to ensure the system's
proper operation at all times.
Comentários a estes Manuais