SPECIAL UL REQUIREMENTS
UL 1610 GRADE AA CENTRAL STATION MERCANTILE BURGLARY
INSTALLATIONS USING DERIVED CHANNEL
IMPORTANT!:
Requires the use 01 No. 4140ATX Control.
NOTE: Not a UL Listed application.
BELL CONNECTIONS Audible alarms must be provided by the use of AB12 Bell in Box,.The AB12
must be mounted so that it can be heard outside the protected area.
INSTALLATION NOTES
1. All wiring between AB12 and 4140ATX must be in conduit, and all
conduit holes (knockouts) on the Control panel shall be used or blocked
from access. (See Diagram 38,414OATX Grade A Installation.)
2. Use 12V 4 AH (minimum) Battery.
3. Value of End-of-line resistor is 1 K ohms (‘41=0).
4. Entry Delays cannot exceed 80 seconds for UL Commercial Burglary
Listings.
5. ~e&tirsout cannot be less than 18 minutes for UL Commercial Burglary
6. If 419OWH Dual Point RPMs are used, tamper detection in Piekf Address
‘24 must be enabled (enter 0).
7. Field ‘16 Confirmation of Arming Ding must be enabled.
8. Field ‘18 AC Loss Alarm after 4 hours must be enabled.
9. Field ‘27 24 Hour Test must be enabled.
10. Open/Close reporting must be enabled.
-.
Diagram 39. COMMERCIAL GRADE AA CENTRAL STATION 4140ATX CONNECTED TO No. 696UL STU
ADEMCO’s
VISTA
XM SERIES TECHNICAL REFERENCE MANUAL