ZONE 1
STSTEbi CONFIGURATION (PERIPIH3bU.S~
4 1
- C. SMOKE DETECTOR CONFIGURATIONS -
When programmed as an EOLR supervised FIRE zone (type 09 in program
field ‘02) up to three O-wire smoke detectors can be used. Recommended
are the BRK1400 ionization detector, 2400 Photoelectric smoke detector,
and the 24OOTH Photoelectric smoke detector with 135°F heat sensor.
l
FOLLOW INSTRUCTIONS FOR INDIYIDUAL SMOKE DlTEClDRS FOR PROPER INSTAUATION
AND WIRING.
*USE BAK MODEL 1400.2400. OR 240Vt.H ONLYI
Diagram 20. ZONE 1 EOLR SUPERVISED FOR O-WIRE SMOKE DETECTORS
ADVISORY
If the EOLR is not at the end of the loop, the zone is not fully supervised. The
system will not respond to an open circuit within the zone.
ZONES 2 THROUGH 8
These zones can suppart as many 4-wire Smoke detectors
as
can be
powered, when programmed as a FIRE zone, type 09, in program field ‘02.
There
are
only two requirements: (1) The zones must be configured for
EOLR supervision, and (2) A normally-closed, momentary Switch must be
Installed in series with the power to the detectors in order to allow reset of the
smoke detectors after an alarm. The detectors must be wired in parallel, with
the EOLR at the last detector, for full supervision. as shown:
ANY ZONE.2THRUS
TB2
.
USE OF RELAY
SMOKE
DETECTORS
I
II II
lmo OHM
END OF LINE
RESISTOR
FOLLOW INSTRUCTIONS FOR INDIVIDUAL SUDKE DEMXDRS FOR PRDPER INSYALLATIDN AND WIRING
FDR CtRtXJll AND PDWER
D&gram 21. ZONES 2-8 EOLR SUPERVISED FOR CWIRE SMOKE DETECTORS
ADEMCO’s
VISTA XM SERIES TECIYNICAL REFERENCE
MANUAL
WWW.DIYALARMFORUM.COM