ADEMCO 5130XM Manual de Instruções Página 115

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 159
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 114
114 TROUBLESHOOTING
- B.
HARD-WIRED ZONES, l-9 -
PTOM
Zone 1 in trouble
(“CHECK”)
Zones 2-8 not detecting
faults when their EOLRs
are shorted (READY
display stays on)
Zone 9 Is indicating
a fault (“READY” will
not appear)
Zone 9 false alarms
perlodically
Zones l-9 not detecting
faults (READY light
stays on)
ACTlON
If programmed for fire or burglary using open-circuit sensors, a 13.000
ohm EOLR must be used across the zone, at the last device, as
described in the SYSTEM CONFIGURATION: ZONES section.
If using EOLRs, check that program field ‘41=0; if not using EOLRs,
‘41-l.
This zone ls for closed circuit, unsupervised use only. Do not use open
circuit devices or an EOLR on this zone.
This zone has a response time of 6-l 0 milliseconds, and should be used
with ‘Fast response’ devices, such as vibration sensors or glass break
sensors, only. If devices with a response time of greater than 10
milliseconds are used, the zone may false alarm due to contact %ounce”,
if used in areas where vibrations may occur.
Check program fields 1’16 and 1’19 to make sure the wired zone(s) in
question have not been enabled as RF zones.
ADEMCO’s VISTA XM SERIES TECHNICAL REFERENCE MANUAL
WWW.DIYALARMFORUM.COM
Vista de página 114
1 2 ... 110 111 112 113 114 115 116 117 118 119 120 ... 158 159

Comentários a estes Manuais

Sem comentários